Hladilni polhermetični kompresor 2-stopenjski S6F-30.2Y
Hladilni polhermetični kompresor 2-stopenjski S6F-30.2Y
Vrsta kompresorja | Kond.temp. | Qo / Pe | Temperatura izhlapevanja °C | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
[°C] | -20 | -25 | -30 | -35 | -40 | -45 | -50 | |||||
S6F-30.2Y | 30 | Qo | 44450 | 36250 | 29200 | 23200 | 18060 | 13650 | 9820 | |||
Pe | 17,41 | 16,43 | 15,32 | 14,06 | 12,63 | 11,02 | 9,20 | |||||
35 | Qo | 42700 | 34800 | 28050 | 22250 | 17280 | 12980 | 9220 | ||||
Pe | 18,91 | 17,74 | 16,44 | 14,99 | 13,37 | 11,56 | 9,56 | |||||
40 | Qo | 40900 | 33350 | 26900 | 21300 | 16510 | 12330 | 8630 | ||||
Pe | 20,40 | 19,09 | 17,61 | 15,96 | 14,12 | 12,07 | 9,82 | |||||
45 | Qo | 39100 | 31900 | 25700 | 20400 | 15760 | 11700 | |||||
Pe | 21,87 | 20,44 | 18,80 | 16,95 | 14,85 | 12,50 | ||||||
50 | Qo | 37250 | 30400 | 24600 | 19490 | 15040 | ||||||
Pe | 23,31 | 21,79 | 20,02 | 17,96 | 15,57 | |||||||
55 | Qo | 35450 | 29050 | 23500 | 18610 | |||||||
Pe | 24,71 | 23,11 | 21,23 | 18,97 |
BITZER dviguje lestvico v smislu tehnologije in zmogljivosti za razširjene nizkotemperaturne aplikacije z 2. generacijo 2-stopenjskih kompresorjev.Ta serija je rezultat obsežnih raziskav na podlagi dolgoletnih izkušenj pri izdelavi visoko učinkovitih in trdnih batnih kompresorjev.Kontrola pretoka plina in delovni ventili so posebej prilagojeni za uporabo pri nizkih temperaturah.
Tukaj napišite svoje sporočilo in nam ga pošljite